大金空调适配器

 

1. 适配器状态查询

  发送: 01 04 00 00 00 01 31 CA

  响应: 01 04 02 00 00 B9 30

2. 室内机连接状态

  发送: 01 04 00 01 00 04 A0 09

  响应: 01 04 08 00 00 00 00 00 00 00 00 24 0D

3. 室内机通信状态

  发送: 01 04 00 05 00 04 E1 C8

  响应: 01 04 08 00 00 00 00 00 00 00 00 24 0D

4. 室内机连接状态和室内机通信状态

  发送: 01 04 00 01 00 08 A0 0C

  响应: 01 04 10 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 55 2C 

5. 尝试一种错误码

  发送: 01 05 00 00 00 01 0C 0A

  响应: 01 85 02 C3 51 

6. 读取32001即室内机性能信息(室内机地址为1-00),三个寄存器

  发送: 01 04 03 E8 00 03 30 7B

  响应: 01 04 06 00 00 00 00 00 00 60 93 

7. 读取32001即读取室内机性能信息(连续16个寄存器,不过已经超过了4台VRV室内机了,依旧可以正常通信,难道是室内机的不存在时,不算吗)

  发送: 01 04 03 E8 00 0F 30 7E

  响应: 01 04 1E 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 DA 3E 

8. 读取室内机状态信息(室内机地址为1-00),6个寄存器

  发送: 01 04 07 D0 00 06 70 85

  响应: 01 04 0C 00 00 00 00 00 00 00 00 00 00 00 00 95 B7

9. 读取室内机状态嘻嘻(室内机地址从1-00到1-05),36个寄存器

  发送: 01 04 07 D0 00 24 F0 9C

  响应: 01 04 48 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 00 8B 0C

10. 预置单个寄存器42003即2002,设置温度为26.5度

  发送: 01 06 07 D2 01 09 E9 11

  响应: 01 06 07 D2 01 09 E9 11 

11. 预置多个寄存器

  发送: 01 10 07 D2 00 04 60 87   (数据格式明显是错误的)

  响应: 01 90 03 0C 01 

  发送: 01 10 00 1D 00 04 08 01 23 04 56 07 89 0A BC D7 5F

  响应: 01 90 02 CD C1 

 

posted @ 2016-08-04 13:51  mrsandstorm  阅读(880)  评论(0编辑  收藏  举报