ABB AC900F学习笔记52:Freelance_Mounting_and_Installation_AC_900F_Controller-12

3.2.3 CM 772F PROFIBUS-DP Master Interface
CM 772 RROFIBUS主站接口
 
 
 
 
     The number of possible slaves is determined by the total number of input and output bytes. As a rule, many PROFIBUS PA devices (few I/O bytes) or a limited number of remote I/O (many I/O bytes) can be connected to the bus.
     能够接入的从站数量由输入和输出总字节数决定。通常,许多 PROFIBUS PA 设备(带有很少 I/O 字节)或数量有限的远程 I/O(许多 I/O 字节)可以连接到总线。
Features
 
Protocol
协议
PROFIBUS-DP master V0/V1
PROFIBUS-DP主站
Fieldbus connection
现场总线连接
D-SUB, 9-pin, female connector
9针,母头
Internal power supply
内部供电
Via coupler bus
通过耦合器总线
LEDs
LED总线
Five LEDs for status display
5个LED状态灯
Use
用于
AC 700F
AC 900F (not with PM 904F)
AC 700F和不含PM 904F的AC 900F
Form factor
外形
AC 700F
Controller redundancy support
对融域控制器的支持

NO

Hot plug
热插拔

NO

HCIR

NO

LED status displays
LED状态显示灯
      After having been switched on, the CI 772 PROFIBUS module performs a self-test during power-up. If the test is successfully performed, the yellow LED RDY lights up, if not, the LED starts to flash and the initialization is aborted. If the LED RDY does not light up at all, the PROFIBUS module is probably defective. During initialization, with newly configured modules or after a change of the operating mode, all LEDs may light up briefly before reaching the defined status.
        送电后,CI 772模板开始自检。如果自检成功执行,黄色的RDY(准备好)灯亮起,如果自检没通过,starts闪烁,终止初始化工作。如果RDY灯没有亮起,可能是这个PROFIBUS模块由问题。在初始化过程中,使用新配置的模块或在操作模式更改后,所有 LED 可能会在达到定义状态之前短暂亮起。

LED

LED灯

Color

颜色

Status

状态

Meaning

含义

PWR

电源灯

Green

绿色

ON

Voltage is applied
已送电

OFF

No voltage is applied
未送电

RDY

准备好

Yellow

黄色

ON

Coupler ready for operation
耦合器准备工作
Cyclic flashing
周期闪烁
Boot loader is active
耦合器准备就绪
Non-cyclic flashing
无周期闪烁
Hardware or system error
硬件或系统错误

OFF

Defective hardware
硬件缺陷

RUN

运行灯

Green

绿色

ON

Communication on
通讯中
Cyclic flashing
周期闪烁
Ready for communication
准备通讯
Non-cyclic flashing
无周期闪烁
Parameterization error
参数化错误

OFF

No communication
没有通讯

STA

状态灯

Yellow

黄色灯

ON

DP master: data or token are transmitted via the network
DP主站:数据或令牌通过网络传输

OFF

DP master: No token
DP主站:没有令牌

ERR

错误灯

Red

红色

ON

PROFIBUS error
PROFIBUS错误

OFF

No error
没有错误