ABB AC900F学习笔记48:Freelance_Mounting_and_Installation_AC_900F_Controller-8

3.1.4 LED display and control elements
LED显示和控制元素
 
LEDs and switches
LED和开关
 
The LEDs on the front panel show essential status information and diagnostic data. The operating mode can be changed using the switches。
前面板上的LED灯显示基本状态信息和诊断数据。操作模式可以通过开关来更改。
 
LED COLOR STATUS Meaning

PWR

电源灯

Green

绿色

ON

Power supply correctly connected, 24V DC voltage
is applied 
电源正确连接24VDC电源

OFF

No supply voltage
Power supply not correctly connected
没有电源电压
电源接线不正确

ERR

错误灯

RED

红色

ON

Hardware error during self-test
自检时发生硬件错误

Flashing

闪烁

Error occurred, LED continues to flash until the
system is stopped or started again
有错误发生,LED连续闪烁直到系统停止或者重启
 

OFF

No error
没有错误

Orange

橙色

Flashing

闪烁

Write or read operation on the SD card
SD卡上有读写操作

RUN

运行灯

Green

绿色

ON

AC 900F is operating RUN
AC900F正在运行

Red

红色

ON

AC 900F was stopped STOP
AC900F停止

P/S

主备灯

Green on
Primary
“主”控制器灯橙色亮

ON

In redundant configurations, the active AC 900F is
referred to as Primary.
Synchronous operation as normal state 
在冗余配置下,此运行的AC900F为“主”
同步操作为正常状态

Flashing

闪烁

Non synchronous operation as transition state;
occurs when the data are not aligned with the
Secondary 
 
非同步操作,为正在同步的过渡状态。
当主备数据不一致的时候发生
Orange on Secondary
“备”控制器橙色灯亮

ON

Synchronization mode
同步模式

Flashing

闪烁

Synchronization on
正在同步
Red on Secondary
“备”控制器红色灯亮

ON

Redundancy synchronization failed 
冗余同步失败
OFF 灭
No redundancy configured没有冗余配置

BATT

电池灯

GREEN 绿色

ON

Sufficient battery capacity for the indicated
buffering time
足够的电池容量以满足指定的缓冲时间
Red  红色

ON

Battery test during power-up 
上电时的电池测试
Empty battery
空电池
Battery not connected 
有电池,但电池未接线
 
Orange  橙色

ON

The battery must be replaced.
电池必须更换
Three switches are provided for the following functions: 
三个面板开关提供下面的功能:
– RUN/STOP 运行/停止切换
– TOGGLE (Primary/ Secondary) 主备切换
– RESET 重启
 
RUN/STOP switch
运行停止开关
This switch is used to start and stop the program sequence. In redundant mode, the position of the RUN/STOP switch on the active AC 900F is used.
此开关用于启动和停止程序序列,也就是决定要不要运行程序序列。主AC900F控制器上RUN/STOP切换开关在使用,也就是说去拨备用控制器上这个开关时不能启动/停止程序序列的。
 
     Both controllers perform the command (Run or Stop). The LED display on the Primary shows the current status. In the case of a redundancy change-over, the last status is retained irrespective of the RUN/STOP switch position.
     两个控制器执行命令(运行或者停止)。主控制器上的LED指示灯显示当前状态,当冗余切换时,无论运行/停止切换位置如何,都保留最后一个状态。
 
Change-over to Run 转换到运行
             
       Normal operation. The program sequence is started. If the module is reset and a self-test is subsequently started, no configuration menu appears at the diagnostic interface。

        正常操作。程序序列已启动。如果模块重置,随后开始自检,则诊断接口中不会显示配置菜单。

Change-over to Stop  转换到停止
       
        The program sequence is stopped. If the module is reset and a selftest is subsequently started, the configuration menu appears at the diagnostic interface.

        程序序列已停止。如果模块重置,随后开始自检,则配置菜单将显示在诊断界面。

 
TOGGLE switch
主备切换开关
     With a redundant AC 900 F configuration in synchronized state, a change-over of the TOGGLE switch on the Primary produces the following effect: The previous Secondary changes immediately to Primary and the previous Primary to Secondary without requiring any system rebooting. Any actuation of the TOGGLE switch on the Secondary will be ignored.
    配置为同步状态下的冗余AC 900F,“主”控制器上的切换开关拨动或产生下面的效果:以前为备用的(控制器)立即成为主(控制器),以前为主(控制器)的立即成为备(控制器),这无需任何系统重启。在备用控制器上拨这个开关将被忽略。
 
RESET switch
重启开关
       The RESET switch is used to reset the AC 900F. Depending on the system status,either a warm or a cold start is initiated. A “tool“ (e.g. a ball pen or similar) is required to actuate the RESET switch。
重启开关用于AC900F的重启。根据系统状态,要么是热启动,要么是冷启动。执行 RESET 开关需要"工具"(例如球笔或类似工具,这应该是为了防止误触)
 
When the RESET switch is pressed for a specified time, the following functions will be released:
当重启开关持续按下以下时间时,下列功能将执行
Single controller
单控制器
< 4 s = Warm start 
小于4秒,热启动
> 4 s = Cold start
大于等于4秒,冷启动
 
Redundant controller
冗余控制器
< 4 s = no function
小于4秒,啥也不做
> 4 s = redundancy change-over and cold start of the controller with actuated RESET switch
大于等于4秒,冗余切换,该控制器冷启动
 
SD card reader
SD读卡器
 
      The SD card reader is used for data backup, for restoring the application as well as for updating the firmware. Additional to this, a backup of the project file can be exported from Freelance Engineering to the SD Card (details see Engineering Manual System Configuration). All high-quality SD cards with 1 GB up to 32 GB are supported. With an appropriate adapter, mini and micro SD cards can be used as well. 
       SD读卡器用于数据备份,为恢复应用程序和升级固件。此外,项目文件的备份能够冲工程师站导出到SD卡。(详细信息请参阅工程手册系统配置)支持从1GB到32GB的高质量SD卡。使用合适的适配器,迷你和微型 SD 卡也可以使用。
During a write or read operation on the SD card, the error LED flashes orange on
the AC 900F.
当SD卡做读写操作时,AC900F上的错误指示灯橙色闪烁。
To avoid data loss or inconsistent data, the SD card must not be removed during a
write or read operation, the power supply must not be interrupted and no
redundancy toggle should be performed
为避免数据丢失或者数据不一致,在读写操作时,SD卡不能取出,电源不能中断,不能冗余切换。
 
 
 